An OT incident response plan is a short document that answers five questions before anything happens. Who can cut the link between IT and OT? Which lines can keep running without IT? How do engineers reach the plant if the corporate network is down? Which evidence do we keep? How do we check the machines before restarting?
Most plants already have an IT incident response plan. It usually assumes that the right move is to shut down infected systems. On the plant floor that move can stop a process mid-batch, damage equipment or create a safety issue. The OT plan exists to handle that difference.
How OT incident response differs from IT
The goal in OT is a safe process state. In IT, the goal is to protect data, so teams isolate and reimage machines. In OT, a controller that keeps running a known program is often safer than a controller that is powered off. The decisions involve operations, maintenance and safety staff, and sometimes the equipment vendor.
Most plant stoppages start in IT. In many ransomware cases, the controllers were never touched. Production stopped because the MES, the ERP, the domain controllers or the shared jump server were encrypted, or because the company chose to stop as a precaution. A useful OT plan therefore spends as much time on dependencies on IT as on attacks against the machines.
Guidance exists and is free. NIST SP 800-82 Rev. 3 covers incident response for OT. The SANS ICS incident response poster gives a one-page workflow. CISA publishes the #StopRansomware guide with a response checklist. Use them as the base and adapt them to your plant.
The five decisions to write down before an incident
1. Who can isolate OT from IT, and how. Name one role per shift, with the authority to act without a phone call to headquarters. Write the exact step: which rule, which route or which cable. If every path between IT and OT goes through one point, such as an industrial DMZ, the step is one action in one place.
2. Which lines can run without IT. For each line, write down what it needs from IT: recipes, work orders, label printing, quality data, time sync, authentication. Then decide whether it can run in manual mode, for how long, and with how many extra people.
3. How engineers and vendors reach the plant when IT is down. If remote access depends on the corporate VPN and the corporate directory, it disappears with them. Plan a second path with its own internet link, its own accounts and MFA, and session logging.
4. Which evidence to keep. Keep firewall and gateway logs, remote session logs, and copies of affected HMI and engineering workstations before anyone reimages them. Investigators and insurers will ask who connected to what, and when.
5. How to check the machines before restarting. Keep offline copies of PLC programs, HMI projects and network device configurations. After an incident, compare what is running with those copies before restarting.
Containment options in OT
| Situation | Containment step | Effect on production |
|---|---|---|
| Ransomware on the IT network only | Cut the IT/OT link at the industrial DMZ | Lines keep running; MES and ERP data stop flowing |
| Infected engineering workstation in one cell | Isolate that cell's switch port or zone | The cell runs on its local HMI; no program changes |
| Suspicious remote session to a machine | End the session and disable that account | None, if the session was only maintenance |
| Unknown change on a controller | Put the line in a safe state, compare with the offline copy | Line stops until the logic is verified |
Practice the first row. Cutting IT from OT is the step most plants need, and it is the one they hesitate to take because nobody has done it before. A planned test during a maintenance stop removes that hesitation.
Keeping access to the plant when the corporate network is down
This is the step most plans leave out. When IT is encrypted, the corporate VPN, the directory and often the email system are gone. The plant still needs engineers, integrators and sometimes the machine builder to look at a controller.
Prepare a separate path: an internet link that does not go through the corporate network, accounts that do not depend on the corporate directory, MFA, and a gateway that logs each session. Test it during a planned stop, so the first time it is used is not the day of the incident.
At the IT/OT boundary, Access Gate IDMZ puts every path between IT and OT through one appliance. Isolating the plant becomes one change in one place, and the session log shows who reached which machine during the incident.
Restarting after an OT incident
Restart one line at a time. Before each restart, compare the controller logic and HMI project with the offline copy, check that safety instrumented systems were not modified, and reset every account used during the incident. Watch the process values for a full cycle before moving to the next line.
Reconnect IT last. Bring the IT/OT link back only after the IT side is declared clean, and open the flows one by one: historian first, then MES, then remote access.
Testing the plan
Run a tabletop exercise twice a year with operations, maintenance, IT and your main vendors. Pick a realistic scenario, such as ransomware on the office network on a Friday night. Walk through each of the five decisions and write down what was missing.
Once a year, test one step for real during a planned stop: cut the IT/OT link, run a line in manual mode, or open the out-of-band access path. Then run a post-incident review, as described in our guide to post-incident analysis in OT.
Related reading
- Running the plant when IT is down after ransomware
- Using NetFlow and logs for ICS threat hunting
- Example incident response process (template)