The short version
A plant can keep running while corporate IT is encrypted, if the plan is made before the attack. In most ransomware cases, the PLCs and drives are fine. Production stops because the plant depends on IT services around the machines, or because nobody can prove OT is clean.
The plan has five parts. Decide which lines can run in island mode. Move the services OT needs from IT into the OT network. Keep offline backups of PLC and HMI projects. Give operations a pre-approved isolation step. Plan a way for engineers and vendors to reach OT without the corporate network. Then exercise it.
This post covers each part, with three public cases and the CISA and NIST guidance behind them.
Why plants stop when only IT is encrypted
Three public cases show the pattern: the attack hits IT, and production stops anyway.
Norsk Hydro, March 2019. LockerGoga ransomware locked thousands of servers and PCs across the aluminum producer. According to Microsoft's account of the incident, production lines stopped at some of Hydro's 170 plants. Several extrusion plants in Europe and the US halted temporarily. Other plants switched to manual procedures. Retired employees came back to run the old paper process. At a plant in Portland, Oregon, workers ran machines by hand to fill specific orders. Hydro did not pay the ransom and restored its data from backups.
Colonial Pipeline, May 2021. DarkSide ransomware hit the company's IT network. Colonial said it "proactively took certain systems offline to contain the threat, which has temporarily halted all pipeline operations" (BleepingComputer). The joint CISA and FBI advisory AA21-131A states there were no indications the attacker moved to OT systems. The pipeline stopped as a precaution.
Clorox, August 2023. Clorox found unauthorized activity on some of its IT systems. Its September 2023 8-K filing says the company began manual ordering and processing at a reduced rate of operations. By the date of that filing, production had resumed at "the vast majority" of its manufacturing sites, with a ramp up to full production over time.
The pattern continued in 2025. Steelmaker Nucor reported unauthorized access to "certain information technology systems" and said it "temporarily and proactively halted certain production operations at various locations" (Nucor 8-K, May 2025).
In each case, the cause of the stop sat outside the controllers. Manufacturing remains the main ransomware target in industry, as the 2026 ransomware data for manufacturing shows, so this is worth planning for.
What stops, why, and what to prepare
Most stops trace back to a short list of IT dependencies. Walk through it with your OT lead and your plant IT lead.
| What stops | Why it stops | What to prepare |
|---|---|---|
| Production scheduling and work orders | MES or ERP runs on the IT network or in a data center reached through IT | Local copies of the current schedule, recipes and work orders, on paper or a standalone PC |
| Operator and engineer logins | HMIs and engineering stations authenticate against corporate Active Directory | A separate OT directory or local accounts, with credentials kept offline |
| Name resolution and time | OT servers use corporate DNS and NTP | DNS and a time source inside the OT network |
| Remote support | Engineers and vendors reach the plant through the corporate VPN and an IT jump server | A separate path into OT that does not use the corporate network |
| Labels, lot tracking and quality release | Label printing and traceability pull data from ERP | A manual procedure agreed with quality, and pre-printed stock |
| The whole plant, as a precaution | Nobody can confirm OT is clean, so leadership stops everything | A pre-approved isolation step and written criteria for island mode |
Decide which lines can run in island mode
Island mode means a line runs with the connection to the corporate network cut. The controllers, HMIs and local servers keep working on their own.
Decide this line by line, before an incident. For each line, write down three things. What does it need from IT to run a shift? How long can it run on local data? Who approves running it in island mode?
Some lines cannot run safely without a system that lives on IT. Write that down too. A clear "this line stops" is better than a debate during an incident. The CISA and FBI advisory AA21-131A makes the same point: identify IT and OT interdependencies, develop workarounds or manual controls, and regularly test manual controls.
Move the OT dependencies inside the OT network
Every IT service a line needs to run is a reason it stops when IT is down. Reduce that list.
Give OT its own directory, or local accounts on HMIs and engineering stations. Run DNS and a time source inside the OT network. Keep the recipes, the current production schedule and open work orders on a local server or printed binder. Update those copies on a fixed schedule, for example at each shift change.
The goal is that the plant can finish today's orders without reaching anything on the IT side. MES and ERP can catch up after recovery.
Keep offline copies of PLC and HMI projects
If ransomware reaches an engineering workstation, the PLC programs and HMI projects on it are gone. The controllers may keep running, but you cannot change or restore them.
Export PLC programs, HMI projects, drive parameters, switch and firewall configurations and historian settings. Store the copies offline, away from any network the ransomware could reach. Label each copy with the date and the firmware version it matches.
Then test a restore on a spare controller or a bench setup. The #StopRansomware Guide from CISA, the FBI, NSA and MS-ISAC asks for offline, encrypted backups, tested in a disaster recovery scenario, and "golden images" of critical systems. For engineering workstations, a golden image is the fastest way back.
Give operations a pre-approved isolation step
Cutting the IT/OT connection should be one documented action that operations can execute. At Colonial, the shutdown was a decision taken under uncertainty. A pre-approved step gives you another option: isolate OT and keep the lines running.
Write the step down. Name who can trigger it, usually the plant manager or operations director with the OT lead. Describe the exact action, such as disabling one interface or pulling one cable. Keep the procedure on paper, since the #StopRansomware Guide asks for a hard copy and an offline version of the response plan.
This is easier when IT reaches OT through one controlled boundary. Many plants have several paths: a firewall, a dual-homed PC, a vendor modem, a shared VLAN. Each one is a separate thing to cut under pressure.
Access Gate IDMZ puts the IT/OT boundary in one appliance. Every path between IT and OT goes through it, so isolation is one change in one place. Its session log shows who reached which machine, and when. The response team can use that log to check what crossed the boundary before the cut.
Plan a way in for engineers when corporate IT is down
When the corporate network is down, the usual remote paths go with it. The VPN, the jump server and the directory behind them may all sit on IT. Engineers at home and vendors on the phone cannot reach the plant.
Plan a separate path that does not depend on the corporate network. Prepare three things:
- A separate internet link, such as a cellular router kept for this purpose.
- Separate accounts with MFA that do not rely on corporate Active Directory.
- A gateway on the OT side that limits each person to the machines they need and logs every session.
If the IT/OT boundary already runs through Access Gate IDMZ, that gateway is in place. Connect the out-of-band link to it, and the same per-machine rules, MFA and session log apply to vendors and engineers during the incident. Set the path up and test it before you need it. Access Gate does not stop ransomware. It controls and records who reaches OT while IT is rebuilt.
Test the plan with an exercise
A plan nobody has rehearsed will not hold up on the day. Run a tabletop exercise at least once a year with operations, plant IT, quality and a key vendor.
Start from a realistic scenario: corporate IT is encrypted at 3 a.m. on a Tuesday. Walk through the first shift. Who calls whom, and on which phone? Which lines go to island mode? Who executes the isolation step? Where are the offline backups, and who can restore them?
Then test one part for real. Run one line in island mode for a shift, or restore one PLC program from backup. NIST SP 800-184 covers recovery planning, playbooks and testing. NIST SP 800-82 Rev. 3 covers incident handling for OT. Our guide to building an incident response plan for ICS covers the full plan structure.
Where to start this month
Start with the list of dependencies. It takes one meeting and it shows where the plan is thin.
- List each line's IT dependencies with the table above.
- Export and store offline copies of every PLC and HMI project.
- Write the isolation step and name who can trigger it.
- Decide how engineers reach OT when the corporate VPN is down.
For the IT/OT boundary and its session log, see Access Gate IDMZ.